AUTO MAINS (Utility) FAILURE CONTROL MODULES, PN. 6020-003-03 DSE

Code: AUTO MAINS (Utility) FAILURE CONTROL MODULES, PN. 6020-003-03 DSE
PART NO : 6020-003-03
DESC : AUTO MAINS (Utility) FAILURE CONTROL MODULES
BRAND : DSE

Rp11,000,000

Stok 1

Stok 1

Deskripsi

PART NO : 6020-003-03
DESC : AUTO MAINS (Utility) FAILURE CONTROL MODULES
BRAND : DSE
USE : STANDART ENGINE AND ELECTRONIC CAN-BUS VARIANTS
INFO :
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING : 8 V to 35 V Continuous
CRANKING DROPOUTS : Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT : 100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT : 60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT : 40 mA at 12 V, 35 mA at 24 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE : 15 V to 415 V AC (Ph to N), 26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE : 3.5 Hz to 75 Hz
INPUTS
DIGITAL INPUTS A to F : Negative switching
ANALOGUE INPUTS A to C : Configurable as:
Negative switching digital input : 0 Ω to 480 Ω
ANALOGUE INPUT D
Configurable as : Negative switching digital input
0 V to 10 V, 4 mA to 20 mA, 0 Ω to 480 Ω
OUTPUTS
OUTPUT A (FUEL) : 10 A short term, 5 A continuous, at supply voltage
OUTPUT B (START) : 10 A short term, 5 A continuous,at supply voltage
AUXILIARY OUTPUTS C, D, E & F : 2 A DC at supply voltage ­­